Sola/Hevi-Duty Products
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps and Distributors
Product Specials

PDF Links
Selection Guide
Specifications


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.


Home > Products > Uninterruptible Power Systems > S4K Industrial > S4K4U & 6U UPS

S4K 4U (6 kVA) and 6U (10 kVA) Industrial Online UPS

The S4K4U6000 and the S4K6U10000 Industrial UPS Series are the first true on-line industrial UPS that provide flexible output voltage, an integrated maintenance bypass switch and internal batteries all in a slim 4U (7.0”) and 6U (10.5") enclosures.

Both series feature double conversion topology providing the ultimate in protection against a wide range of potential power problems. The S4K4U design of two 3 kVA, 120V inverters inverters allow flexible output voltage to meet mixed load voltage requirements. The UPS automatically configures the output voltage to match the input configuration without requiring tap selections. Self diagnostics simplify maintenance and troubleshooting, and the UPS can be serviced by the customer. The standard maintenance bypass switch provides an additional level of protection.

The S4K4U and S4K6U also feature wide input voltage windows to support the critical load without having to transfer to the battery. This extends system availability when back-up is truly needed.

On this page: Features, Specifications, Battery Specifications, Battery Run Times, Optional Equipment, Manuals

Applications

• Industrial Computers
• Robotics and process controls
• Industrial Automation Systems
• Network servers
• Enterprise telecommunication systems
• Printing and publishing machinery
• Industrial and commercial machinery
• Pharmaceutical and medical diagnosis equipment
• Micro processor controlled equipment
• Mission Critical devices

 

Features Top
 
  • True double conversion technology
  • Automatic frequency detection (60 or 50 Hz)
  • Both models offer 208/120V or 240/120V
  • Power Factor Correction
  • Configurable as a Tower or Rack mount model
  • Self-Diagnostics simplify maintenance and troubleshooting
  • Highest density: 6 kVA in only 4U and 10 kVA in only 6U of rack space
  • Remote Emergency Power Off (REPO)
  • Easily installed in 18" to 32" deep rack using rack mount kit #SRS1832
  • Intellsilot Communication Port
  • User replaceable, hot-swappable internal battery module
  • Built in Serial Communications and Closure Signals
  • Extended Battery Cabinets

  • Compatible with most standby generators
  • Includes both automatic and manual maintenance bypass switch
   
Specifications Top
 
Catalog Number S4K4U6000  S4K6U10000 
 Model Rating 4200W/6000VA at 120/240
(180° only - phase angle)
8000W/8660VA at 120/208 (120 or 240° only)
4200W/5200VA at 127/220
(120 or 240° only - phase angle) *
8000W/10000VA at 120/240 (180° only)*
4200W/5200VA at 120/208 (120 or 240° only - phase angle) 8000W/8660VA at 127/220 (120 or 240° only)
4200W/6000VA at 115/230 (180° only - phase angle)* 8000W/10000VA at 115/230 (180° only)*
3780W/5400VA at 110/220 (180° only - phase angle)* 7200W/9000VA at 110/220 (180° only)*
3360W/4800VA at 100/200 (180° only - phase angle)* 6400W/8000VA at 100/200 (180° only)*
Dimensions -  inches (mm) / Weight - lbs (kg)
Unit (W x D x H)  6.9 x 24.2 x 16.9 (176 x 615 x 430)
10.5 x 29 x 16.93 (267 x 737 x 430)
Shipping (W x D x H) 13.2 x 27.8 x 20.9 (335 x 705 x 530) 16.5 x 34.3 x 22.8 (420 x 870 x 580)
Approx. Shipping Weight - lbs (kg) 76.3 (34.6) 118 (53.6)
  Input AC Parameters
 Nominal Operating Frequency 50 or 60 Hz (Factory Default = 60)
 Factory Default VAC 208 VAC at 120° phase angle (neutral required)
 L1-L2 Factory Default Input Phase Angle 120°

 Allowable Input Phase Angle

120, 180, 240°, Auto-sensing on application of AC
(Restrictions for L-N voltages other  than 120 VAC)

 Factory Default L1-N, L2-N VAC 120 VAC nominal
 User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC (May be modified using configuration program)

L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)

 100% - 90% loading
90 VAC - 140 VAC
 90% - 70% loading
80 VAC - 140 VAC
 70% - 30% loading
70 VAC - 140 VAC
 30% - 0% loading
60 VAC - 140 VAC

L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)

 100% - 70% loading 80 VAC - 140 VAC
 70% - 30% loading 70 VAC - 140 VAC
 30% - 0% loading 60 VAC - 140 VAC
 L1-N, L2-N Max. Allowable VAC 150 VAC
 Input Frequency w/o Battery Operation 40 - 70 Hz
 Input Power Connection Hardwire Terminal Block 3W + G (L-L-N-G)
Output AC Parameters
 Factory Default VAC 120/208 VAC @ 120° phase angle
 L1-L2 Factory Default Output Phase Angle 120°
 Allowable Output Phase Angle 120, 180, 240° Auto-sensing on initial application of input AC 
 Factory Default L1-N, L2-N VAC 120 VAC nominal
 User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC, ±3%
 Output Connections Hardwire Terminal Block 3W + G (L-L-N-G)
 Frequency 50 Hz or 60 Hz, Nominal
 Waveform Sinewave
 Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Bypass Protection Limits
 Disable Bypass operation
If input voltage exceeds ±15% of the nominal voltage
 Re-enable Bypass operation
If input voltage returns to within ±10% of nominal output voltage
 Disable Bypass operation
When the input frequency prevents synchronous operation
Environmental
 Operating Temp +32°F to +104°F (0°C to +40°C)
 Storage Temp +5°F to +122°F (-15°C to +50°C)
 Relative Humidity 0% to 95%, non-condensing
 Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
 Storage Elevation 50,000 ft. (15,000 m) maximum
 Audible Noise <55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides
Agency
 Safety UL 1778, c-UL Listed (Suitable for computer room applications)
 RFI/EMI FCC Part 15, Subpart B, Class A
 Surge Immunity IEEE/ANSI C62.41 Category A & B
 Transportation ISTA Procedure 1A

 

Battery Specifications Top

Internal Battery

Model Number S4K144INTBAT S4K288INTBAT (2 required)
 Used w/ UPS Model S4K4U6000 S4K4U10000 AND S4K288BAT

 Shipping W x D x H - in. (mm)

13.4 x 27.2 x 13.4
(340 x 690 x 340)

11.0 x 24.8 x 16.5
(280 x 630 x 420)

 Unit Weight lbs (kg)  79 (35.8)  78.1 (35.5)
 Shipping Weight lbs (kg)  84 (38.1)  83.6 (38)
 Type Valve-regulated, non-spillable, flame retardant, lead acid
 Quantity x V x Rating 12 x 12V x 9.0 AH (2) x 12 x 12V x 9.0 AH
 Battery Mfg / Part # Yuasa / REW 45-12 FR
 Back-Up Time See Battery Run Time Charts
 Recharge Time 6 Hours to 90% capacity after full discharge into 100% load

External Battery

Model Number S4K144BAT S4K288BAT
 Used w/ UPS Model S4K4U6000  S4K4U10000 
Dimensions & Weights
 Unit (with bezel)
W x D x H - in (mm)
3.5 x 24.2 x 17
(87 x 618 x 430)
7.0 x 27 x 16.93
(178 x 686 x 430)
 Shipping W x D x H 10.5 x 27.2 x 23
(268 x 692 x 585)
13.0 x 34.3 x 22.8
(330 x 870 x 580)
Weight - lbs (kg)
 Unit 93.6 (42.5)
41.6 (18.9)
 Shipping 105 (47.6) 50.6 (23)
Battery Parameters
 Type Valve-regulated, non-spillable, flame retardant, lead acid
 Qty x V x Rating 12 x 12V x 9.0 AH (2) x 12 x 12V x 9.0 AH
 Battery Mfg / Part # Yuasa / REW 45-12 FR
 Back-Up Time See Battery Run Time Charts
Environmental
 Operating Temp
+32°F to +104°F (0°C to +40°C)
 Storage Temp +5°F to +122°F (-15°C to +50°C)
 Relative Humidity 0% to 95%, non-condensing
 Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
 Storage Elevation 50,000 ft. (15,000m) maximum
Agency
 Safety UL 1778, c-UL Listed (Suitable for computer room applications)
 RFI/EMI FCC Part 15, Subpart B, Class A
 Transportation ISTA Procedure 1A

 

Battery Run Times Top

 

Battery/
External
Cabinets
Load %
6000VA
Run Time
in inutes
10000VA
Run Time
in inutes
Battery/
External
Cabinets
Load % 6000VA
Run Time
in Minutes
10000VA
Run Time
in Minutes
Internal Battery 10% 75 107 Internal Battery + 3 External Battery Cabinets 10% 313 494
20% 38 52 20% 183 265
30% 25 31 30% 133 191
40% 18 22 40% 103 119
50% 14 16 50% 82 92
60% 11 13 60% 67 75
70% 9 10 70% 55 62