Sola/Hevi-Duty
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps and Distributors
Product Specials

PDF Links
Selection Guide
Specifications


PDF files require Acrobat Reader
to view them.
Click above to download it
for free.

 

Products
Home > Products > Uninterruptible Power Systems > S4K Industrial

S4K5U International Online UPS Series

The S4K5U6000-5 Industrial On-Line UPS Series is designed for international usage and provides flexible output voltage, an integrated maintenance bypass switch and internal batteries all in a slim 5U (8.7") enclosure.

The S4K5U features true On-Line (double conversion) topology providing the ultimate in protection against a wide range of potential power problems. Flexible output voltages (220/230/240 Volt) are available through the configuration program to allow for international use.  One of the three L-N output voltages is selected to match the local voltage.  Self diagnostics simplify maintenance and troubleshooting, and the UPS can be serviced by the customer. The standard maintenance bypass switch provides an additional level of protection.

The S4K5U also features a wide input voltage window to support the critical load without having to transfer to the battery. This extends system availability when back-up is truly needed.

On this page: Features, Specifications, Battery Specifications, Battery Run Times, Manuals

 
Features Top

  • True double conversion technology
  • Automatic frequency detection of either 60 or 50 Hz
  • Flexible L-N output voltage (220/230/240V)
  • Power Factor Correction
  • Configurable as a Tower or Rackmount model
  • Self-Diagnostics simplify maintenance and troubleshooting
  • Highest density, 6 kVA in only 5U of rack space
  • Remote Emergency Power Off (REPO)
  • Easily installed in 18" to 32" deep rack using rack mount kit #SRS1832
  • Intellsilot Communication Port
  • User replaceable, hot-swappable internal battery module
  • Built in Serial Communications and Closure Signals
  • Matching 4U Extended Battery Cabinets

  • Compatible with most standby generators
  • Includes both automatic and manual maintenance bypass switch

 

Specifications Top

 

Model Number S4K5U6000-5
 Model Rating 6KVA / 4,200W
Dimensions inches (mm)
 Unit (W x D x H)  8.7 x 21.5 x 16.9 (221 x 547 x 430
 Shipping (W x D x H)  22.05 x 27.17 x 19.7 (560 x 690 x 500)
 Shipping Weight - lbs (kg)  175.3 (79.5)
Input AC Parameters
 Nominal Operating Frequency 50 or 60Hz (Factory Default = 50)
 Factory Default VAC 230VAC
 User Configurable VAC 220/230/240VAC (May be modified using configuration program)
 Operating Voltage Range Without  Battery Operation  176 – 276VAC
 Maximum Allowable VAC 276VAC
 Input Frequency Without Battery  Operation 40 - 70Hz
Input Power Connection  See Power Distribution Box
Output AC Parameters
 Factory Default VAC 230VAC
 Output Connections  See Power Distribution Box
 Frequency 50Hz or 60Hz, Nominal
 Waveform Sinewave
 Main Mode Overload >200% for 96 milliseconds; 131 - 199% for 2 seconds; 112- 129% for 10 seconds with transfer to bypass
Battery Parameters
 Type Valve-regulated, non-spillable, lead acid
 Quantity x V 20 x 12V
 Battery Mfr. / Part # Yuasa / REW 28-12
 Back-up Time  See Battery Run Times Table
 Recharge Time (Internal Batteries) 3 hrs. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
 Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
 Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
 Disable Bypass operation When the input frequency prevents synchronous operation 
Power Distribution Box
 Amps Rating 32 Amps
 Input Power Connection 3-Wire Hardwired, 6-10mm2 (8-10AWG)
 Output Power Connection 3-Wire Hardwired, 6-10mm2 (8-10AWG)
 Includes: Two IEC320 C19  16A/250V sockets, Manual Bypass Switch with Indicator Lamps
 Input Branch Circuit Breaker 32A, Supplied by User
Environmental
 Operating Temperature 0°C to +40°C (+32°F to +104° F) 
 Storage Temperature  -15°C to +50°C (+5°F to +122° F)
 Relative Humidity 0-95% non-condensing
 Operating Elevation            Up to 2000m (6600 ft) at 40°C (104° F) without derating  
 Storage Elevation 15,000m (50,000 ft.) maximum
 Audible Noise <55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides
Agency
 Safety EN62040-1-1; TUV/GS (pending approval)
 EMI/EMC/C-Tick EMC EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive
 ESD EN61000-4-2, Level 4, Criteria A
 Radiated Susceptibility EN61000-4-3, Level 3, Criteria A
 Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
 Surge Immunity EN61000-4-5, Level 3, Criteria A
 Transportation ISTA Procedure 1B

 

Battery Specifications Top

External Battery

Model Number S4K240BAT
Used w/ UPS model S4K5U6000-5
Dimensions - inches (mm)
Unit with bezel (W x D x H) 6.9 x 20.55 x 16.9 (176 x 522 x 430)
Shipping (W x D x H)  22 x 27.2 x 17.9 (560 x 690 x 455)
Weight - lbs (kg)
Unit 145 (65)
Shipping 173.1 (78.5)
Battery Parameters
Type Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V 20 x 12V
Battery Manufacturer, Part # Yuasa / REW 45-12
Backup Time See Battery Run Times charts
Environmental
Operating Temp 0°C to +40°C (+32°F to +104° F) 
Storage Temp  -15°C to +50°C (+5°F to +122° F)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 2000m (6600 ft.) at 40°C (104° F) without derating
Storage Elevation 15,000m (50,000 ft.) maximum
Agency
Safety EN62040-1-1; TUV/GS
Transportation ISTA Procedure 1B

 

Battery Run Times Top

 

Battery/External Cabinets Load% 6000VA
Internal Battery (minutes) 10% 94
20% 46
30% 29
40% 21
50% 17
60% 13
70% 11
80% 9
90% 8
100% 7
Internal Battery +1 External Battery Cabinet (minutes) 10% 222
20% 124
30% 81
40% 60
50% 49
60% 39
70% 33
80% 28
90% 24
100% 21
Internal Battery +2 External Battery Cabinets (minutes) 10% 350
20% 197
30% 135
40% 105
50% 85
60% 70
70% 58
80% 50
90% 43
100% 38
Internal Battery +3 External Battery Cabinets (minutes) 10% 478
20% 269
30% 185
40% 145
50% 123
60% 101
70% 85
80% 73
90% 63
100% 55
Internal Battery +4 External Battery Cabinets (minutes) 10% 606
20% 341
30% 235
40% 184
50% 156
60% 131
70% 113
80% 97
90% 85
100% 75

 

 