S5K Modular Series Uninterruptible Power Systems (UPS)
| This
easily upgradeable and flexible UPS provides the protection you want, when you need it.
The 5K Modular is scalable from 4 to 20 KVA, offering many flexible options by adding a few
standard modules. Designed to be fully configured, tested and shipped in the configuration you need,
the 5K Modular also has the ability to be easily upgraded in the field to either higher VA ratings
(up to 20 KVA maximum), longer runtimes or to add N+x parallel redundancy. Configurations can be
cost-effectively upgraded keeping your 5K Modular current without a large reinvestment in a new
system.
The optional N+x redundancy provides a fault-tolerant group of power modules and controls.
The modular design is easy to upgrade so the UPS can grow with the needs of the system that is
being protected.
Each of the modular components, including 4 KVA power modules, battery modules and system control
modules, can be hot-swapped making it easy to increase power, extend your backup runtime or add
redundancy while still providing power protection to the load. |

|

|
| This
fault-tolerant system uses intelligent power and battery modules
which take themselves off-line if there is a problem
without interrupting power to the load. Self-diagnostic capabilities
simplify maintenance and troubleshooting. Each unit incorporates
an internal automatic bypass.
|
- Network servers
- Enterprise
telecommunications systems
- Clusters
of PCs or workstations and peripherals
- LAN gateways,
bridges and routers
- Mini-computers,
superservers and server clusters
- RAID
arrays and other large-scale data handling system
- Scalable for
capacity, redundancy, or battery run time offering unbelievable
flexibility
- Built-in intelligence
is provided for each individual module using microprocessor controls,
increasing functionality, communications and reliability
- N+x parallel redundancy is easily achieved by adding extra control, power and battery modules
- Any failed module will automatically take itself off-line while the other modules continue to
support the connected equipment
- Multiple and
simultaneous communication ports
- Variable input
voltage range minimizes battery operation to increase battery
life
- An automatic
internal bypass for maximum availability of output power
- Continuous
sinewave output
- Power factor
corrected input reduces reflected distortion and optimizes utility
power
- Two-year limited
warranty
(Includes factory start up)
The S5K Modular has two
chassis available to build on.
-
The "A" chassis can accommodate up to 8 modules
- The
"B" chassis can accommodate up to 12 modules and supplies
16 KVA of power with N+1 redundancy
- The
"C" chassis can accommodate up to 12 modules and supplies
a full 20 KVA of power with N+1 redundancy
System control modules are not included
in module count. All chassis can accommodate up to two system control modules. Select the proper chassis
based on your futures need for expansion or redundancy. In most standard (non-redundant) applications,
the A chassis is the most popular.
- Determine the maximum KVA you will need for future expansion.
- Determine the KVA and run time value for your immediate need.
- Determine if you need redundancy. If the exact run time is the critical need, use the
fully redundant option (see Selection
Charts).
- Select the unit that meets both your immediate requirements, and is expandable to your
future needs in the "Maximum Upgrade" column in the selection table. The Maximum
Upgrade column shows the highest KVA expansion that particular configuration is capable of
without removing any of the battery modules from the original configuration.
| Description |
Value |
|
Capacity
(VA/Watts)
|
4
KVA / 2.8 kW to 20 KVA /
14 kW in 4 KVA / 2.8 kW increments |
| Dimensions
- inches |
| Unit
(H x W x D) |
8
module capacity ""A"" Chassis 41""
x 20"" x 28""
12 module capacity ""B"" Chassis 54""
x 20"" x 28"" |
| Shipping
(H x W x D) |
56"
X 32" X 42" |
| Input
AC Parameters |
| Voltage
Range (typical) |
170-276
VAC Low line limit variable with load
170 VAC from 80 to 100% load
144 VAC from 20 to 90% load
127 VAC from 20 to 70% load
100 VAC at less than 30% load |
Voltage
Configuration
and Connection |
Single
phase, 2-wire plus ground (L1-L2-G) |
| Frequency |
60
Hz nominal
40 - 70 Hz range without operating from battery |
| Input
Connector |
Hardwired
only |
| Power
Factor |
.98
typical |
| Output
AC Parameters |
| Voltage |
240,
208, 240/120 (120-0-120 ) or 208/120(120-0-88) |
| Receptacles |
Optional
with use of external Maintenance Bypass |
| Voltage
Regulation |
±
3 % |
| Voltage
Distortion |
Maximum
3% THD for linear loads,
maximum 7% THD for full non-linear loads. |
| Transient
Response |
<
7% for 100% step load; recovery within 96 ms. |
| Frequency |
60
Hz |
| Frequency
Slew Rate |
Selectable
up to 5 Hz/sec |
| Frequency
Sync |
Selectable
up to ±5 Hz |
| Range
Overload |
100
to 110% for 10 minutes minimum
111 to150% 10 seconds
151 to 200% for 2 Cycles |
| Battery
Parameters |
| Battery
Type |
Sealed,
lead acid |
| Recharge
Rate |
3
to 5 hours to 90% capacity |
| Battery
Runtime |
See
Selection Tables for specific configurations
Autonomy time is 6 minutes with an equal number of battery &
power modules in a non-redundant configuration at full load |
| Battery
Voltage |
120
VDC Nominal |
Maximum
charge
current (full load) |
3A |
| Environmental |
Operating
Temperature |
+32oF
to +104oF (0oC to +40oC) |
| Storage
Temperature |
+5oF
to +122oF (-15oC to +50oC) |
| Relative
Humidity |
0%
to 95%, non-condensing |
| Operating
Elevation |
Up
to 10,000 ft. (3000m) at 104oC (40oC)
without derating |
| Storage
Elevation |
15.000m
(50,000 ft.) maximum |
| Heat
Dissipation |
1062
BTU / hour per fully loaded power module (4 KVA / 2.8 kW) |
|
Audible
Noise
|
<
62 dBA @ 1 meter |
| Agency |
| Safety |
UL
1778 listed; c-UL |
Compliant
Immunity
Standards |
ANSI
C62.41, Class A & B |
| Routine
Maintenance |
Keep
the UPS clean and cool to enhance system reliability. Occasionally
clean or replace the fan intake filters to ensure proper airflow.
Do not use liquid or aerosol cleaning fluids. Periodically
review the UPS alarm logs.
|
See Selection Charts for
other options.
| KVA/kW |
P/N#
(Standard) |
P/N#
(Redundant) |
Runtime
(Min@FL/HL) |
| 4 / 2.8 |
S5KA4N1A6 |
S5KA4R1A6 |
7 / 18 |
| 8 / 5.6 |
S5KA8N2A6 |
S5KA8R2A6 |
7 / 18 |
| 12 / 8.4 |
S5KA12N3A6 |
S5KA12R3A6 |
7 / 18 |
| 16 / 11.2 |
S5KA16N4A6 |
S5KB16R4A6 |
7 / 18 |
| 20
/ 14 |
S5KC20N5A6 |
S5KC20R5A6 |
7 / 18 |
The Sola 5K modular is available in many
combinations. Use the part number template below to identify the
description of any given part number.
| Series Designation |
Chassis
Size |
KVA
Rating |
Unit
Type |
Number
of Battery Modules |
Output
Voltage |
Frequency |
| A
= 8 Module Capacity |
4,
8, 12, 16 or 20 KVA
00
= External Battery
n |
N
= Standard
(Not Redundant) |
*
Must be at least one per 4 KVA of capacity
n
|
A
= 208/120
1 x 1
n
|
6
= 60 Hz |
| B
= 12 Module, 16 KVA Capacity |
R
= Redundant
Power & Control |
5
= 50 Hz |
| C
= 12 Module, 20 KVA Capacity |
X
= Redundant Power, Battery
& Control |
X |
| D
= External Battery Cabinet |
B
= Battery
Cabinet
|
Example: 4 KVA Load, Future Expandable to 16 KVA with 7 minutes of runtime.
What is the part number? |
| S5K |
A |
4 |
N |
1 |
A |
6 |
| nResulting
Catalog Number is "S5KA4N1A6".n |