The SDU Off-Line DIN Rail UPS
series combines an industry leading compact design with a wide
operation temperature range and unique installation options.
This cost effective protection solution provides ride through
during brief power outages. This allows critical and sensitive
equipment to safely shut down during extended power failure
preventing costly data losses, work interruptions and equipment
damage. These units include easy to wire screw terminations for
critical devices needing battery back up such as computer-based
control systems.
A printable version of the following sections is available by selecting the
pdf file to the left.
UPS automatic shutdown if overload
exceeds 105% of nominal at 20 seconds, 120% at 10 seconds, 130% at 3 seconds
Short
Circuit
UPS output cut off immediately
Battery Parameters
Battery
Type
Sealed, Non-spillable,
maintenance-free lead acid batteries
Transfer
Time
4 - 6 ms typical.
Back-up
Time* (minutes)
4
2
4
2
Recharge
Time
8 hours to 90% capacity after full
load discharge
Environmental
Operating
Temperature
32°F to 122°F (0°C to 50°C)
Storage
Temperature
5°F to 140°F (-15°C to 60°C)
Relative
Humidity
1% to 95%, non-condensing
Ambient
Operation
1-95% humidity non-condensing,
0-50°C up to 5,000 ft (1500m)
Audible
Noise
< 40dBA (1 meter from surface)
Standards
Safety
UL 1778 C-UL Recognized for
industrial applications, Overvoltage category 3, pollution
degree 3. FCC Part 15, Subpart
B, Class A
EMC: EN50091-2 LVD: EN62040-1-1,
CE Marked
Elevation
5000 ft without derating
Shock
& Vibration
According to the International
Safe Transit Association standard ISTA 2A.
Mounting
To be mounted on DIN TS35/7.5 or
TS35/15 rail system. Chassis mounting permissible via optional
brackets. Unit handles normal shock and vibration of industrial
use and transportation without coming
off rail.