SCL Series Specifications

A printable version of the following sections is available by selecting the pdf file to the left.

Selection Top
Catalog 
Number
Description Output Voltages
V1 V2 V3
VDC A VDC A VDC A

 4 Watt Linear DC Power Supply; DIN Rail Mount

 SCL4D12-DN Dual O/P ± 12V 12 0.13 -12 0.13 - -
 SCL4D15-DN Dual O/P ± 15V 15 0.1 -15 0.1 - -

 10 Watt Linear DC Power Supply; DIN Rail Mount

 SCL10D12-DN Dual O/P ± 12V 12 0.35 -12 0.35 - -
 SCL10D15-DN Dual O/P ± 15V 15 0.3 -15 0.3 - -
 SCL10T512-DN Triple O/P, 5V ± 12V 5 0.2 12 0.3 -12 0.3
 SCL10T515-DN Triple O/P, 5V ± 15V 5 0.2 15 0.25 -15 0.25
Note: Dual output units can be series connected for 24V or 30V applications.

 

Specifications Top

Parameter

Condition

Value

Input

 Vin: AC Input Voltage x

1

115/230 ± 10% VAC Field Selectable
 fin: Input Frequency
47-63 HZ
 Iin: Input Current 115/230V
10 Watt: 0.2 A/0.1 A max
4 Watt: 0.1 A /0.05A max
 Efficiency
Typ. 50%
 Filtering
10 Watt Only: VDE 0871/B

Output

 DVout: Trimming
Fixed, preset
 DVNF: Ripple
Vin=min, Iout=max, 25°C
<5 mVpp
 DVHF: Noise
Vin=min, Iout=max, 25°C
<5 mVpp
 Regulation Accuracy
100...50%, 25°C
<0.05%
 tR: Load Regulation Timing
10...90...10%, 25°C
100 ms
 Temperature Coefficient
Ta=-25...+65°C
0.01%/K typ.
 th: Holdup Time
min. 20 ms

 Overload/Short Circuit

continuous
General
 Conducted Emmissions
EN55011, Level B
 Inducted Noise
ESD
EN61000-4-2, Level 4
HF
ENV50140 (10 V/m)
Burst
EN61000-4-4, Level 4
 Visol p/s: Isolation Voltage (input/output)
TA=25°C
3.0kVAC, EN60950
 Risol: Isolation Resistance
V=230 VAC, 50 Hz
>100 MOhm
 Llea: Leakage Current
2 cm side, middle case
<0.05 mA
 TA: Operating Temperature
10 W: -20...+70°C
4W: -25...+70°C
 Derating
3%/K
 TS: Storage Temperature
TA = 50°C
-40...+85°C

 Cooling

Convection
 Weight (lbs/g)
10W: 1.2 lbs (550g)
4W: 0.44 lbs (200g)
 Case Material/Potting
UL94-VO
 CSA Power Supply Class
Level
 SELV
Protection Class
Class 2

 

Dimensions (mm/inches) Top

SCL 4 Watt Linear


SCP Low Profile Power Supply Mechanical

   

     SCL 10 Watt Linear


SCP Slim Line Power Supply Mechanical


Pin-Out Top

SCL-4

1 2 3 4 5 6

7

8
 Dual
12/15 V
COM 12/15V
-12/-15V
IN
IN
IN

SCL-10

1 2 3 4 5 6

7

8
 Dual
-12/15V
GND 12/15V
12/15V
IN
IN
IN
 Triple
-12/15V
5V
GND 12/15V
COM 5V
12/15V
IN
IN
IN