SCP-X Extreme Environment
Power Supply |
|
|
| The SCP-X is a rugged power supply designed for use in extreme environments. The metal case reduces costs by eliminating separate enclosures. Quick change connectors simplify connectivity for distributed I/O devices on industrial machinery. This model provides 24 Vdc output with limited power to meet Class 2 requirements. Three models are
currently offered based on application.
Features
- IP66/67 Versatile/NEMA 4X Rated
- 24 Vdc, 115/230 Vac, 3.8A Nominal Current
- Listed power supply for stand alone applications
- Can be mounted in any orientation without limitation
- Universal input
- High ambient temperature up to 60oC without derating
- DC OK Green LED
- Worldwide approvals
- Five Year Warranty
|
 |

9HAO
IND. CONT. EQ.
Also listed I.T.E.
Power Supply |

E234790
Class 1 Zone 2
AEx nA IICT4
Ex nA IICT4 U |

DEMK0 06 ATEX 05 21715U
EEX nA IIC T4 U
-40ºC ≤ Tam ≤ +60ºC
|
|
|
|
A printable version of the following sections is available by selecting the
pdf file to the left.
|
Chassis Mount (-CM) Applications
This extreme environment power supply is ideal for outdoor
or wet chassis-mount applications (Figure 1).
• Input connector: 3-pole, male receptacle externally threaded
with ½-14 NPT mounting thread.
• Output Connector: 4-pole, female receptacle externally
threaded with ½-14 NPT mounting thread.
Control Power (-CP) Applications
The SCP100S24X-CP is designed for Control Power
applications where a grounded power supply output is
required (Figure 2).
• Input connector: 3-pole, male receptacle externally threaded
with ½-14NPT mounting thread.
• Output connector: 4-pole, female receptacle internally
threaded with ½-14 NPT mounting thread.
DeviceNetTM (-DVN) Applications
The SCP100S24X-DVN is designed for DeviceNetTM applications where an isolated output from ground is
required (Figure 2).
• Input connector: 3-pole, male receptacle externally threaded
with ½-14NPT mounting thread.
• Output connector: 4-pole, female receptacle internally
threaded with ½-14 NPT mounting thread.
|
|
|
|
|
|
Catalog Number |
Description |
Approx. Ship
Weight lbs (kg) |
SCP-DINBKT |
Mounting bracket to secure SCP-X
to
DIN Rail (included) |
1 (.45) |
|
| Selection Guide |
 |
Catalog Number |
Output Current |
Output Voltage |
Output Power |
Input 3-PIN Connections |
Output 4-PIN Connections |
| SCP 100S24X-CM |
3.8 A |
24 Vdc |
95 W |
Daniel Woodhead
P/N 103000A01FXX0(2) |
Daniel Woodhead
P/N 104002A01FXX0(2) |
| SCP 100S24X-CP |
Turck RSM46*M
*length in meters |
| SCP 100S24X-DVN |
1. Connections to be provided by the user.
2. XX is the length of the cordset in foot. |
| |
* V- is isolated from ground. V- is a separately derived source so it is permissible to bond to group if required in the application.
|
* 0 Vdc connections are internally bonded to ground.
** V- is isolated from ground. V- is a separately derived
source so it is
permissible to bond to group if required in the application.
|
|
Input |
|
Nominal Voltage |
Any voltage from 100 to 240 Vac Input |
|
-AC Range |
85-264 Vac Universal Input |
|
-DC Range |
100-353 Vdc |
|
Nominal Current1 |
1.6A/0.7A |
|
-Inrush current max. |
Typ. <25A |
|
Power Factor Correction2 |
0.95 |
|
Frequency |
50/60/400 Hz |
|
Output |
|
Power Back Immunity |
35V |
|
Overvoltage Protection |
25-25.5 Vdc, autorecovery |
|
Nominal Voltage |
24 Vdc |
|
Tolerance |
< +/-2% overall (combination line, load, time and temperature
related changes). |
|
- Line Regulation |
< 0.5% |
|
- Load Regulation |
< 0.5% |
|
- Time & Temp. Drift |
< 1% |
|
Ripple3 |
< 50mVpp |
|
Nominal Current |
3.8A |
|
Holdup Time |
> 25ms (Full load, 100Vac Input @ Tamb= +25o) to 95% output
voltage |
|
General |
|
Case |
IP66/67 versatile ingress protection; also meets UL50 Type 4X
enclosure. |
|
Min. Required Free Space |
1 in. (25 mm) all sides but mounted base (permissible to mount
in any orientation) |
|
H x W x D (inches/mm) |
4.7 x 7 x 1.8 (119 x 178 x 46) |
|
Weight (lbs/kg) |
2.6 lbs (1.16 kg) |
|
|
|
Emissions |
EN61000-6-3, EN61204-3, EN55022 Class B, EN61000-3-2,
EN61000-3-3 |
|
Immunity |
EN61000-6-2, EN61204-3, EN55024, IEC61000-4-2, IEC61000-4-3,
IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8,
IEC61000-4-11 |
|
Approvals |
UL508, cULus; UL60950, cULus; UL60079-15 cRUus; IEC60950; CE (LVD
73/23 & 93/68/EEC).
(EMC 89/336 & 93/68/EEC). EN61000-3-2,
EN50021 (Class 1, Division 2 Hazardous Location, EEX nA IIC T4 U up to 60°C Ambient.)4
|
|
|
Storage: -40o to +85oC, Operation: -40o to +60oC full power with
linear derating to half power from 60o to 70oC
(Convection
cooling, no forced air required). Operation up to 100% load
permissible with sideways or front side up mounting
orientation. |
|
Humidity |
Up to 100% RH with condensation. |
|
Altitude |
0 to 3,000 meters (0 to 10,000 feet) |
|
Vibration |
1.0 gravity (g) peak, 10-500 Hz (random wave).
Passed random vibration test conditions for 3 axes for 60 minutes duration while energized and operating. |
Shock |
4 g peak, 22 milliseconds half-sine pulse, 3 times on 6 faces while energized and operating |
Warranty |
5 years |
|
MTBF |
>500,000 hours according to Telcoredia/Bellcore SR-332 Issue 1,
(V<in 120Vac, Tamb=40oC) |
|
General Protection/Safety |
Protected against continuous short-circuit, continuous overload,
continuous open circuit. Protection class 1 (IEC536),
degree of
protection IP66/67 versatile (IEC 529). Safe low voltage: SELV
(acc. IEC60950) |
|
Status Indicators - Visual |
DC OK LED |
| Installation |
|
Fusing |
|
|
-Input |
Internally fused, fuses not replaceable |
|
-Output |
Inherently limited current to meet Class 2 requirements per
UL1310 |
|
Mounting |
Chassis mounted via built in mounting tabs. Removal and
replacement of the unit shall be possible from front of panel. |
|
Connections |
Input: 3 pin IP67 molded plug (quick disconnect). Output: 4 pin
IP67 molded receptacle (quick disconnect). |
1. Input current ratings are specified with low input, line conditions, worst case efficiency values and power factor.
2. Power Factor Correction at 50/60 Hz only.
3. Ripple/noise is stated as typical AC values when measured with a 20 MHZ, bandwidth scope and 50 Ohm termination.
4. Additional installation requirements apply when used in hazardous locations (refer to user manual).
|