SolaHD
Home Search
What's New
Products
Cross Reference
Technical Support
Contact Us
Password Protected Area for Reps/Distributors
Product Specials

PDF Links
Specifications


PDF files require Acrobat Reader
to view them.
Click above to download it
for free

Products
Home > Products > Power Protection and Conditioning > TPC Series

Three Phase Power Conditioners

These three phase power conditioners protect equipment from voltage sags and spikes, switching transients, lightning, and induced surges by a carefully designed surge suppression circuit linked to a shielded isolation transformer and input and output filters.

These units hold output voltage regulation to a maximum of ±5%, even with an input voltage window of +15% to -25%. Response time to any line variation is less than 1.5 cycles power factor. The units operate with 150 dB Common Mode noise attenuation and 65 dB Normal Mode noise attenuation at 100 kHz.

TPC Series
On this page: Features, Specifications, Selection Table

cClick here to view certificate.US

A printable version of the following sections is available by selecting the pdf file to the left.

Features Top

  • Provides tight regulation of ±5% for protection against sag (-25%) and swell (+15%) conditions.
  • Control circuit by-pass switch.
  • Status indicating lights.
  • Shielded isolation transformer.
  • UL 544, UL 1012, CULUS Listed.
  • Provides optional step down function.
  • Surge suppression to ANSI/IEEE and IEC Standards
  • High efficiency (97%) microprocessor controlled tap switcher.
  • Automatic over and under voltage protection.
  • High overload capability.
  • Attenuates noise by shielded isolation transformer design.

Specifications Top

Mechanical

 Indicators   Indicating Lamps: 1 red (overtemperature)
 3 green (regulated output present)
 Connections  Field wired, terminal blocks
 Size and Weight  See Selection Table
 Safety Agency Approvals  UL 544 and UL 1012 (60 Hz Models) cUL 
 (Canadian Standard C22.2 No 125) 
 (60 Hz models). Complies with Part 15 Subpart J
 of FCC rules for a Class A computing device.
 Control Circuit
 By-pass Switch
 Switch on front panel can divert input power
 directly to load, bypassing the voltage 
 regulator.

Environmental

 Audible Noise  Less than 50 dBA at 3 feet
 Ambient Temperature  0° to 40°C Operating, 0° to 80°C Storage
 Operating Altitude  10,000 feet without derating
 Operating Humidity  95% relative (non-condensing)

Electrical

 Power Ratings  10, 15, 22.5, 30, 45, 75, 100, 150 KVA,
 Three Phase
 Nominal Voltages  See Selection Table
 Input Voltage Range  -25% to +15% of nominal rated voltage.
 Output Voltage Range  Regulated to ± 5% of nominal voltage with
 an input voltage range of –25% to +15%.
 Response Time   Responds to any line variation in less than 1.5 
 cycles maximum, 1 cycle typical, under any
 condition of line, load or power factor.
 Technology   Microprocessor controlled electronic tap
 switching. 6 taps switched at zero current
 crossing.
 Operating Frequency  57-63 Hz
 Load Power Factor  0.6 leading to 0.6 lagging
 Insulation Resistance  100 megohms from winding to core measured 
 at 500 VDC
 Efficiency  97% typical
 Overload Capability  125% of rated load for 1 minute 200% of rated
 load for 10 seconds 500% of rated load for 
 1 cycle.
 EMI  Less than 0.2 gauss at a distance of 3 ft.
 Mean Time Between Failure (MTBF)  Exceeds 150,000 hours

Protection

 Over / Under Voltage
 (Electronic Fuse*)

 

 

 Output voltage is interrupted should the input 
 voltage exceed the input tolerance of the power
 conditioner for three consecutive cycles.
 Output is automatically reapplied once input
 returns within tolerance window of +10%,
 -20%. *Field replaceable.
 Short Circuit Protection   Input circuit breaker with shunt trip
 Over Temperature Protection  Red lamp indication of overtemperature at approximately 
 180°C, followed by a shutdown (main circuit breaker shunt
 trip) at approximately 193°C.

Noise Suppression Performance

 Common Mode Noise Attenuation  150 dB at 100 kHz
 Normal Mode Noise Attenuation  65 dB at 100 kHz
 Surge Suppression  Tested to ANSI/IEEE standard C62.41 
 (IEEE 587 Cat A and B), 1000-4, 1000-5

 

Selection Table Top

 

Output
KVA
Catalog
Number
VAC
Input
Dimensions
H x W x D (in/cm)
Ship Weight
(lbs/kg)
208 VAC Input, 208Y/120 VAC Output, 60 Hz
10 63T2A310 208 29 x 21 x 19 (73.5 x 53.5 x 48) 265/120
15 63T2A315 208 38 x 24 x 19 (96.5 x 61 x 48) 485/220
22.5 63T2A322 208 38 x 24 x 19 (96.5 x 61 x 48) 530/240
30 63T2A330 208 38 x 24 x 19 (96.5 x 61 x 48) 850/386
45 63T2A345 208 40 x 38 x 28 (101.5 x 96.5 x 71) 940/426
75 63T2A375 208 40 x 38 x 28 (101.5 x 96.5 x 71) 1095/496
100 63T2A410 208 40 x 52 x 28 (101.5 x 132 x 71) 1800/816
150 63T2A415 480 40 x 52 x 28 (101.5 x 132 x 71) 2400/1089
480 VAC Input, 208Y/120 VAC Output, 60 Hz
10 63T2B310 480 29 x 21 x 19 (73.5 x 53.5 x 48) 265/120
15 63T2B315 480 38 x 24 x 19 (96.5 x 61 x 48) 485/220
22.5 63T2B322 480 38 x 24 x 19 (96.5 x 61 x 48) 530/240
30 63T2B330 480 38 x 24 x 19 (96.5 x 61 x 48) 850/386
45 63T2B345 480 40 x 38 x 28 (101.5 x 96.5 x 71) 940/426
75 63T2B375 480 40 x 38 x 28 (101.5 x 96.5 x 71) 1095/496
100 63T2B410 480 40 x 52 x 28 (101.5 x 132 x 71) 1800/816
150 63T2B415 480 40 x 52 x 28 (101.5 x 132 x 71) 2400/1089
600 VAC & 600Y/346 Input, 208Y/120 VAC Output, 60 Hz
10 63T2C310 600 29 x 21 x 19 (73.5 x 53.5 x 48) 265/120
15 63T2C315 600 38 x 24 x 19 (96.5 x 61 x 48) 485/220
22.5 63T2C322 600 38 x 24 x 19 (96.5 x 61 x 48) 530/240
30 63T2C330 600 38 x 24 x 19 (96.5 x 61 x 48) 850/386
45 63T2C345 600 40 x 38 x 28 (101.5 x 96.5 x 71) 940/426
75 63T2C375 600Y/346 40 x 38 x 28 (101.5 x 96.5 x 71) 1095/496
100 63T2C410 600Y/346 40 x 52 x 28 (101.5 x 132 x 71) 1800/816
150 63T2C415 600Y/346 40 x 52 x 28 (101.5 x 132 x 71) 2400/1089
480 VAC Input, 480Y/277 VAC Output, 60 Hz
10 63T2D310 480 29 x 21 x 19 (73.5 x 53.5 x 48) 265/120
15 63T2D315 480 38 x 24 x 19 (96.5 x 61 x 48) 485/220
22.5 63T2D322 480 38 x 24 x 19 (96.5 x 61 x 48) 530/240
30 63T2D330 480 38 x 24 x 19 (96.5 x 61 x 48) 850/386
45 63T2D345 480 40 x 38 x 28 (101.5 x 96.5 x 71) 940/426
75 63T2D375 480 40 x 38 x 28 (101.5 x 96.5 x 71) 1095/496
100 63T2D410 480 40 x 52 x 28 (101.5 x 132 x 71) 1800/816
150 63T2D415 480 40 x 52 x 28 (101.5 x 132 x 71) 2400/1089

 Other voltage configurations are available. Contact Technical Service.


What's New | Products | Cross Reference |
Technical Support | Contact Us | Search | Home

 